DESIGN / CONSTRUCTIONAMBER series ‘PI’ Low Voltage Three Phase Power Capacitors in ‘Impregnated & Protected’ design are manufactured out of Modules made of Low Loss Self-Healing Metallised Polypropylene Film, impregnated in non-PCB oil of low viscosity. The Modules incorporate internal pressure disconnection system which fully protects the Modules against bursting in case of fault. The modular construction allows repair / maintenance of the assembly at the component level.

DISCHARGE RESISTORSFitted to reduce the voltage to a level below 75V within 3 minutes of switch-off.

TERMINATION: Plated Terminals for termination of Cables.

HOUSING: Electrostatic Powder Coated MS sheet, 1 mm, with ample ventilation louvers.

TECHNICAL DATA:

SPECIFICATIONS IEC 60831 (2014-02) Parts 1 & 2 “Shunt Power Capacitors of the self-healing type for AC Systems having a rated voltage up to and including 1000 V”
TEMPERATURE CATEGORY -25°C / D
(Minimum ambient air temperature: -25°C
Maximum ambient air temperature during a year: +55°C
Highest mean over any period of 24 hours: +45°C
Highest mean over any period of 1 year: +35°C)
APPLICATION Indoor, the capacitors are specially suited for environments having consistently high ambient temperatures and high harmonic levels.
RATED VOLTAGES 440 AC
RATED FREQUENCIES  50 Hz
CONNECTIONS Delta
LOSSES Less than 0.5 W / kVAr
CONTINUOUS OVER VOLTAGE 1.1 Un (except transients)
CONTINUOUS OVER CURRENT 1.3 In (except transients)
TEST VOLTAGE Between terminals: 2.15 Un AC for 2 seconds
Terminals to case: 3 kV AC for 10 seconds
TOLERANCE – 5% / +10%
PROTECTION Over-pressure disconnection.
INSTALLATION Vertical, Indoor
kVAr RANGE 12.5 kVAr, 25.0 kVAr & 50 kVAr, for ranges not mentioned here, please enquire.

WARNING: Capacitor replacement may be hazardous since residual voltage may be present across the capacitor terminals. Always discharge capacitors by short-circuiting the terminals with an insulated wire, even though discharge resistors may have been provided.

ATTENTION: Capacitors covered by this catalogue comply with international standards such as IEC, VDE, BS, EN, UL etc. It is the user’s responsibility to take utmost care both in the selection of capacitors for a particular usage, and their correct installation. AMBER shall not be liable for any consequential damages occurring for any reasons what-so-ever.

Note:

  • Due to continuous research and development in our technology, the data and sizes given in this catalogue may be changed without prior notice.
  • Please reconfirm the dimensions with AMBER if this information is crucial for your application.
  • Please contact AMBER for your requirements of non-standard working voltages, capacitance values, container dimensions, lead-lengths, tolerances, etc.

TECHNICAL DATA:

SERIES PI – THREE PHASE – 50Hz
440 Volts
(Capacitance and current values are per phase)
kVAr Container Code Capacitance Rated Current
PI µF Amps
12.5 PI1 68.5 16.4
25.0 PI2 137.0 32.8
50.0 PI3 274.0 65.6
Container Code Dimensions in mm
A B C D E F
PI1 80 240 265 290 250 300
PI2 140 275 320 355 200 295
PI3 140 275 320 355 450 550

 

 

Catalogue Numbers / Ordering Code: Catalogue Numbers are generated as under.

1st and 2nd positions Series code – PI
3rd and 4th positions Voltage code – Working Voltage ÷ 10
5th, 6th, 7th and 8th positions kVAr code – kVAr x 100
9th position Frequency code
A = 50 Hz
B = 60 Hz

Example: If customer has three phases, 50 Hz, 25 kVAr with 440 volts than its ordering code is: PI440250A.

pi-draw-1

0
Connecting
Please wait...
Send a message

Sorry! We aren't around right now. Leave a message and we'll get back to you, asap.